Pre-installation Worksheet
The pre-installation worksheet is a project planning tool designed to expedite map file creation.
Filling Out the Pre-Installation Worksheet
- Obtain the facility floor plan CAD file floor plan (the edited version, with fixtures and network components added).
- Download the pre-installation worksheet interactive PDF from support.digitallumens.com.
- Design the lighting network by completing the worksheet:
- Complete one instance of Table One (see below for example).
- For each network in the system, complete one instance of Table Two (see below for example).
Table One Example
Quantity of Fixtures | 178 | ‹ Enter the total quantity of fixtures you are installing at the facility |
---|---|---|
Quantity of Rooms | 4 | ‹ Enter the total quantity of rooms in which the fixtures will be installed |
Room name | Number of Fixtures | Networks |
---|---|---|
Dry Storage | 42 | A01 |
-20 F Freezer | 36 | A02 |
-10F Freezer (1) | 50 | A03 |
-10F Freezer (2) | 50 | A04 |
^ List room names | ^ Enter the quantity of fixtures to be installed in each room | ^ Assign Network IDs |
Assigning Network IDs
- Assign Network IDs in numerical order beginning with A01 to A16, B01 to B16, and so on.
- Each room containing less than or equal to 50 fixtures should be assigned a unique Network ID.
- Each room containing more than 50 fixtures should be assigned multiple networks, dividing the networks evenly with less than or equal to 50 fixtures.
Note: Do not exceed H16.
Note: Identical network numbers should not be adjacent to one another. For example, do not place B04 next to A04, C04 next to B04, and so on.
Table Two Example (Complete a new table for each network)
Network ID | A01 | ‹ Copy the Network ID from Table One |
---|---|---|
Room (or room portion) | Dry Storage | ‹ Copy the room name from Table One |
Number of Fixtures | 42 | ‹ Copy the quantity of fixtures from Table One |
Zone Area | Number of Fixtures | Active Level (0-100) |
Inactive Level (0-100) |
Sensor Delay (≥30 seconds) |
---|---|---|---|---|
Front Fixtures | 11 | 100 | 10 | 90 sec |
Rear Fixtures | 11 | 100 | 10 | 90 sec |
Aisles 1-6 | 20 | 100 | 0 | 60 sec |
^ Enter Zone Area | ^ Enter Number of Fixtures | ^ Enter rules for each zone | ^ Enter rules for each zone | ^ Enter rules for each zone |
Note: A rule specifies the three settings to a zone (and all fixtures within that zone). The rule specifies active power level, inactive power level, and the sensor delay.